Wilo-VeroLine-IPL
Installation and Operating Instructions  »

Single stage inline, flanged, long coupled, mechanical sealed dry rotor pump

Hot water heating systems, chilled water air conditioning systems, closed cooling circuits, industrial circulation systems
Special features/Product advantages
  • Integral suction diffuser cast in volute inlet (larger models only)
  • Pump flanges 125 # raised face ANSI std (250 # ANSI optional)
  • Cataphoretic coating for corrosion protection
  • Pump feet drilled and tapped for ease of installation
  • All bolts "non-metric"
Wilo-VeroLine-IPL


Technical data

  • Temperature range: 15 °F to + 250 °F (-10 °C to +120 °C)
  • Power supply (smaller horsepower): 1~115/208-230 volt, 60 Hz
  • Power supply (larger horsepower): 3~208-230/460, 575 volt, 60 Hz
  • Motor options: ODP, TEFC, Premium and "Super E" efficiency types, 2 and 4 pole available (3,500 and 1,750 RPM)
  • Flange connection: 1 ½" to 3" with ¼" pressure gauge tappings
  • Maximum operating pressure 145 PSI (10 bar), minimum inlet pressure NPSHreq dependant (see detailed curves)
Equipment
  • Coupled to motor via one piece coupling
  • Standard NEMA frame Baldor motor
Description/Design
  • Single stage low pressure centrifugal, inline design with mechanical seal
  • Baldor NEMA standard motors
Materials
  • Pump volute: cast iron
  • Impeller: engineered composite
  • Shaft: 316L stainless steel
  • Mechanical seal: Q1Q1X4GG (silicium carbide seal faces, HNBR elastomers)
Scope of delivery
  • Pump and motor (optionally pump end only)
  • Installation and operating instructions
Wilo-VeroLine-IPL
Wilo-VeroLine-IPL
Image of the product as EPS (20.7 MB)  »
Wilo-IPL  »
Extract from Catalogue - Wilo-VeroLine-IPL A2  »
Our downloads for the Wilo VeroLine-IPL series
The following documentation is available for your information:

Download
WILO IPL Product Brochure (111 KB) »